Daikin · Heat pumps · Daikin Altherma 3 R F (split heat pump, R32)
8H-01Overheating/undercooling mixed water circuit
Name in the manufacturer's documentation (service manual): Overheating/undercooling mixed water circuit
[1]
In plain words (editorial)
Overheating or undercooling of the mixed water circuit (bizone systems) – for example the mixed water temperature is more than 5 K above setting [9-00]. The manual lists thermistors, the 3-way valve, the bizone PCB, the pump and a clogged circuit.
When to call a service technician: Contact your installer or Daikin dealer.
✎ editorial – written from the cited sources, not a manufacturer statement. Status: draft.
For technicians
Possible causes (source text)
Steps given by the manufacturer (source text)
- Perform a check of the outlet water thermistor bizone[10]
- Check the field setting [9‑00][11]
- Perform a check of the 3-way valve[12]
- Perform a check of the bizone pcb[13]
- Perform a check of the outlet water after backup heater thermistor[14]
- Check if the water circuit is clogged[15]
- Perform a check of the water pump[16]
- Perform a check of the backup heater contactor(s)[17]
⚠ Work on refrigerant circuits, mains electricity and PV DC wiring is for qualified technicians only.
The Polish page has more detail (plain-language explanation, safe checks, guides): Read in Polish →
Sources
Every statement has a footnote to the document and PDF page. “Quote verified” means the quote was found automatically in the text of that page.
- [1] Daikin Altherma 3 R F – ERGA04~08E + EHVH/X04+08S18+23E – Installer reference guide (4P629086-1D (2024.04)) , p. 254 official manufacturer document quote verified
8H-01 Overheating/undercooling mixed water circuit
- [2] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 26 manufacturer document – copy from a distributor quote verified
faulty outlet water thermistor for bizone.
- [3] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 26 manufacturer document – copy from a distributor quote verified
mixed water temperature >[9‑00] setting+5k.
- [4] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 26 manufacturer document – copy from a distributor quote verified
faulty 3‑way valve.
- [5] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 26 manufacturer document – copy from a distributor quote verified
faulty bizone pcb.
- [6] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 26 manufacturer document – copy from a distributor quote verified
faulty outlet water after backup heater thermistor.
- [7] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 26 manufacturer document – copy from a distributor quote verified
clogged water circuit.
- [8] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 26 manufacturer document – copy from a distributor quote verified
faulty water pump.
- [9] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 26 manufacturer document – copy from a distributor quote verified
faulty backup heater contactor(s).
- [10] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 26 manufacturer document – copy from a distributor quote verified
perform a check of the outlet water thermistor bizone.
- [11] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 26 manufacturer document – copy from a distributor quote verified
check the field setting [9‑00].
- [12] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 26 manufacturer document – copy from a distributor quote verified
perform a check of the 3-way valve.
- [13] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 26 manufacturer document – copy from a distributor quote verified
perform a check of the bizone pcb.
- [14] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 26 manufacturer document – copy from a distributor quote verified
perform a check of the outlet water after backup heater thermistor.
- [15] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 26 manufacturer document – copy from a distributor quote verified
check if the water circuit is clogged.
- [16] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 26 manufacturer document – copy from a distributor quote verified
perform a check of the water pump.
- [17] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 26 manufacturer document – copy from a distributor quote verified
perform a check of the backup heater contactor(s).