Haier · Split air conditioners · Haier Flexis Plus (wall-mounted split, R32)
E9Internal unit overload
Name in the manufacturer's documentation (service manual): Internal unit overload
[1]
In plain words (editorial)
Indoor unit overload: in heating the indoor heat exchanger got too hot repeatedly. The service manual lists the expansion valve, a dirty heat exchanger, the sensor or insufficient refrigerant; its first step is to clean the filters.
When to call a service technician: Clean the filters as described in the user manual; if the code returns, call a service technician.
✎ editorial – written from the cited sources, not a manufacturer statement. Status: draft.
For technicians
Detection conditions (source text)
- Activated when the temperature being sensed by the heat exchanger rises above 65℃ twices in 30 minutes[2]
Possible causes (source text)
Steps given by the manufacturer (source text)
⚠ Work on refrigerant circuits, mains electricity and PV DC wiring is for qualified technicians only.
The Polish page has more detail (plain-language explanation, safe checks, guides): Read in Polish →
Sources
Every statement has a footnote to the document and PDF page. “Quote verified” means the quote was found automatically in the text of that page.
- [1] Haier – Service Manual, Model AS35S2SF1FA-BH (Flexis Plus), Version V1, 2020-11-14 (V1 (2020-11-14)) , p. 29 official manufacturer document quote verified
- [2] Haier – Service Manual, Model AS35S2SF1FA-BH (Flexis Plus), Version V1, 2020-11-14 (V1 (2020-11-14)) , p. 41 official manufacturer document quote verified
rises above 65℃ twices in 30 minutes
- [3] Haier – Service Manual, Model AS35S2SF1FA-BH (Flexis Plus), Version V1, 2020-11-14 (V1 (2020-11-14)) , p. 41 official manufacturer document quote verified
Faulty electronic expansion valve
- [4] Haier – Service Manual, Model AS35S2SF1FA-BH (Flexis Plus), Version V1, 2020-11-14 (V1 (2020-11-14)) , p. 41 official manufacturer document quote verified
Dirty heat exchanger
- [5] Haier – Service Manual, Model AS35S2SF1FA-BH (Flexis Plus), Version V1, 2020-11-14 (V1 (2020-11-14)) , p. 41 official manufacturer document quote verified
Faulty heat-exchange sensor
- [6] Haier – Service Manual, Model AS35S2SF1FA-BH (Flexis Plus), Version V1, 2020-11-14 (V1 (2020-11-14)) , p. 41 official manufacturer document quote verified
Insufficient gas
- [7] Haier – Service Manual, Model AS35S2SF1FA-BH (Flexis Plus), Version V1, 2020-11-14 (V1 (2020-11-14)) , p. 41 official manufacturer document quote verified
1) clean the filters
- [8] Haier – Service Manual, Model AS35S2SF1FA-BH (Flexis Plus), Version V1, 2020-11-14 (V1 (2020-11-14)) , p. 41 official manufacturer document quote verified
2) reinstall the fan
- [9] Haier – Service Manual, Model AS35S2SF1FA-BH (Flexis Plus), Version V1, 2020-11-14 (V1 (2020-11-14)) , p. 41 official manufacturer document quote verified
check room temperature and