Haier Flexis Plus: how to view the last fault (emergency key)
Summary (editorial)
Pressing the emergency (urgency) key for a certain time shows the fault record, as described in the service manual.
✎ editorial – written from the cited sources, not a manufacturer statement. Status: draft.
From the manufacturer's documentation (English source wording, with page)
- Under the system off mode, pressing the urgency key for 10 to 15 seconds shows the resume of the last malfunction[1]
- Pressing the urgency key for 5 to 10 seconds in off mode starts the test operation[2]
- Nothing is presented if there is no code list; the malfunction display automatically finishes in 10 seconds[3]
- Some protections (low/high load) are stored in the malfunction resume and not revealed[4]
- The resume restores after the power supply restores[5]
- Trouble record codes are not displayed directly[6]
⚠ Work on refrigerant circuits, mains electricity and PV DC wiring is for qualified technicians only.
The Polish page has more detail (plain-language explanation, safe checks, guides): Read in Polish →
Sources
Every statement has a footnote to the document and PDF page. “Quote verified” means the quote was found automatically in the text of that page.
- [1] Haier – Service Manual, Model AS35S2SF1FA-BH (Flexis Plus), Version V1, 2020-11-14 (V1 (2020-11-14)) , p. 19 official manufacturer document quote verified
press the urgency key for 10 to 15 seconds
- [2] Haier – Service Manual, Model AS35S2SF1FA-BH (Flexis Plus), Version V1, 2020-11-14 (V1 (2020-11-14)) , p. 19 official manufacturer document quote verified
press the urgency key for 5 to 10 seconds
- [3] Haier – Service Manual, Model AS35S2SF1FA-BH (Flexis Plus), Version V1, 2020-11-14 (V1 (2020-11-14)) , p. 20 official manufacturer document quote verified
The malfunction display will automatically finish in 10 seconds.
- [4] Haier – Service Manual, Model AS35S2SF1FA-BH (Flexis Plus), Version V1, 2020-11-14 (V1 (2020-11-14)) , p. 19 official manufacturer document quote verified
malfunction resume and will not be revealed
- [5] Haier – Service Manual, Model AS35S2SF1FA-BH (Flexis Plus), Version V1, 2020-11-14 (V1 (2020-11-14)) , p. 20 official manufacturer document quote verified
The resume restores after the power supply restores.
- [6] Haier – Service Manual, Model AS35S2SF1FA-BH (Flexis Plus), Version V1, 2020-11-14 (V1 (2020-11-14)) , p. 29 official manufacturer document quote verified
Trouble record