Huawei · PV inverters · Huawei SUN2000-KTL-M1 (three-phase inverter, 3–10 kW, battery-ready)

Alarm 2009String Short-Circuited to Ground

Name in the manufacturer's documentation (fault list): String Short-Circuited to Ground[1]

In plain words (editorial)

A PV string is short-circuited to ground, or damp air around the PV array has reduced its insulation to ground. If auto-recovery from this protection is enabled, the alarm clears automatically once the fault is gone.

When to call a service technician: Have an installer measure and repair the PV cable insulation. Contact your installer or Huawei technical support.

✎ editorial – written from the cited sources, not a manufacturer statement. Status: draft.

The Polish page has more detail (plain-language explanation, safe checks, guides): Read in Polish →

Sources

Every statement has a footnote to the document and PDF page. “Quote verified” means the quote was found automatically in the text of that page.

  1. [1] Inverter Alarm Reference (Issue 14, 2026-06-15) (EDOC1100345192 Issue 14) , p. 23 official manufacturer document quote verified 2009 String Short-Circuited to Ground
  2. [2] Inverter Alarm Reference (Issue 14, 2026-06-15) (EDOC1100345192 Issue 14) , p. 23 official manufacturer document quote verified the pv array is short-circuited to the ground.
  3. [3] Inverter Alarm Reference (Issue 14, 2026-06-15) (EDOC1100345192 Issue 14) , p. 23 official manufacturer document quote verified the ambient air of the pv array is damp and the insulation between the pv array and the ground is poor.
  4. [4] Inverter Alarm Reference (Issue 14, 2026-06-15) (EDOC1100345192 Issue 14) , p. 23 official manufacturer document quote verified the negative pv terminal of mppt1 is short-circuited to the ground.
  5. [5] Inverter Alarm Reference (Issue 14, 2026-06-15) (EDOC1100345192 Issue 14) , p. 23 official manufacturer document quote verified the ambient air of the negative pv terminal of mppt1 is damp, and the insulation between the circuit and the ground is poor.
  6. [6] Inverter Alarm Reference (Issue 14, 2026-06-15) (EDOC1100345192 Issue 14) , p. 25 official manufacturer document quote verified for the inverter equipped with an automatic dc disconnect switch, check the dc switch status. if the dc switch points to 'trip', contact your vendor or technical support and then go to the next step.
  7. [7] Inverter Alarm Reference (Issue 14, 2026-06-15) (EDOC1100345192 Issue 14) , p. 25 official manufacturer document quote verified remove the positive and negative pv cables on the inverter. use a megohmmeter to measure the resistance of each pv cable to the ground in sequence. if a short circuit occurs or the insulation resistance is low, check whe…
  8. [8] Inverter Alarm Reference (Issue 14, 2026-06-15) (EDOC1100345192 Issue 14) , p. 25 official manufacturer document quote verified if no faults are detected in the pv cables using the megohmmeter, check each pv cable for damage and rectify the fault.
  9. [9] Inverter Alarm Reference (Issue 14, 2026-06-15) (EDOC1100345192 Issue 14) , p. 25 official manufacturer document quote verified after the fault is rectified, manually clear the alarm. if the fault persists, contact your vendor or technical support.
  10. [10] Inverter Alarm Reference (Issue 14, 2026-06-15) (EDOC1100345192 Issue 14) , p. 25 official manufacturer document quote verified check the resistance between the negative pv terminal of mppt1 and the ground. if a short circuit or insufficient insulation is found, rectify it.
  11. [11] Inverter Alarm Reference (Issue 14, 2026-06-15) (EDOC1100345192 Issue 14) , p. 25 official manufacturer document quote verified if auto recovery from string-to-ground short-circuit protection is disabled, check and rectify the preceding faults, and manually clear the alarm.
  12. [12] Inverter Alarm Reference (Issue 14, 2026-06-15) (EDOC1100345192 Issue 14) , p. 25 official manufacturer document quote verified if auto recovery from string-to-ground short-circuit protection is enabled, the alarm will be automatically cleared after fault recovery.