Huawei · PV inverters · Huawei SUN2000-KTL-M1 (three-phase inverter, 3–10 kW, battery-ready)
Alarm 2067Faulty power collector
Name in the manufacturer's documentation (fault list): Faulty power collector
[1]
In plain words (editorial)
The inverter has lost communication with the power meter, or the meter's CT or PT is disconnected. The manual says to check the meter model and RS485 settings, its power supply and the RS485 cable.
When to call a service technician: Have your installer check the meter and its wiring.
✎ editorial – written from the cited sources, not a manufacturer statement. Status: draft.
For technicians
Possible causes (source text)
Steps given by the manufacturer (source text)
- Check whether the configured power meter model is the same as the actual model.[5]
- Check whether the communications parameters for the power meter are the same as the rs485 configurations of the device.[6]
- Check whether the power meter is powered on and whether the rs485 communications cable is connected correctly.[7]
- Check whether the power supply to the power meter is abnormal due to a power grid failure. 2 check whether the ct is correctly connected to the meter. 3 check whether the pt is correctly connected to the meter.[8]
⚠ Work on refrigerant circuits, mains electricity and PV DC wiring is for qualified technicians only.
The Polish page has more detail (plain-language explanation, safe checks, guides): Read in Polish →
Sources
Every statement has a footnote to the document and PDF page. “Quote verified” means the quote was found automatically in the text of that page.
- [1] Inverter Alarm Reference (Issue 14, 2026-06-15) (EDOC1100345192 Issue 14) , p. 61 official manufacturer document quote verified
2067 Faulty power collector
- [2] Inverter Alarm Reference (Issue 14, 2026-06-15) (EDOC1100345192 Issue 14) , p. 61 official manufacturer document quote verified
the power meter communication is interrupted.
- [3] Inverter Alarm Reference (Issue 14, 2026-06-15) (EDOC1100345192 Issue 14) , p. 61 official manufacturer document quote verified
the ct is disconnected from the meter.
- [4] Inverter Alarm Reference (Issue 14, 2026-06-15) (EDOC1100345192 Issue 14) , p. 61 official manufacturer document quote verified
the pt is disconnected from the meter.
- [5] Inverter Alarm Reference (Issue 14, 2026-06-15) (EDOC1100345192 Issue 14) , p. 61 official manufacturer document quote verified
check whether the configured power meter model is the same as the actual model.
- [6] Inverter Alarm Reference (Issue 14, 2026-06-15) (EDOC1100345192 Issue 14) , p. 61 official manufacturer document quote verified
check whether the communications parameters for the power meter are the same as the rs485 configurations of the device.
- [7] Inverter Alarm Reference (Issue 14, 2026-06-15) (EDOC1100345192 Issue 14) , p. 61 official manufacturer document quote verified
check whether the power meter is powered on and whether the rs485 communications cable is connected correctly.
- [8] Inverter Alarm Reference (Issue 14, 2026-06-15) (EDOC1100345192 Issue 14) , p. 61 official manufacturer document quote verified
check whether the power supply to the power meter is abnormal due to a power grid failure. 2 check whether the ct is correctly connected to the meter. 3 check whether the pt is correctly connected to the meter.