LG · Heat pumps · LG Therma V Monobloc (air-to-water heat pump)
CH01Problem in remote room air sensor
Name in the manufacturer's documentation (service manual): Problem in remote room air sensor
[1]
In plain words (editorial)
Problem with the remote room air sensor. The service manual names an incorrect connection between the sensor and the PCB (heater), a faulty PCB or the sensor itself; the technician checks the sensor resistance and voltage.
When to call a service technician: Contact an LG-authorised service technician or your installer.
✎ editorial – written from the cited sources, not a manufacturer statement. Status: draft.
For technicians
Possible causes (source text)
Steps given by the manufacturer (source text)
- Resistance: 10 kΩ at 25 centigrade (unplugged) →for Remote room air sensor[5]
- Resistance: 5 kΩ at 25 centigrade (unplugged) →for all sensors EXCEPT remote room air sensor[6]
- Voltage: 2.5 V DC at 25 centigrade (plugged) (for all sensors)[7]
- Refer resistance-temperature table to check in different temperature[8]
⚠ Work on refrigerant circuits, mains electricity and PV DC wiring is for qualified technicians only.
The Polish page has more detail (plain-language explanation, safe checks, guides): Read in Polish →
Sources
Every statement has a footnote to the document and PDF page. “Quote verified” means the quote was found automatically in the text of that page.
- [1] LG Therma V Monobloc – Installation manual (MFL68026607 Rev.21) (MFL68026607 Rev.21_062126) , p. 277 official manufacturer document quote verified
1 Problem in remote room air sensor
- [2] LG Therma V Monobloc – Installation manual (MFL68026607 Rev.21) (MFL68026607 Rev.21_062126) , p. 277 official manufacturer document quote verified
Incorrect connection between sensor and PCB(Heater).
- [3] LG Therma V Monobloc – Installation manual (MFL68026607 Rev.21) (MFL68026607 Rev.21_062126) , p. 277 official manufacturer document quote verified
PCB(Heater) fault
- [4] LG Therma V Monobloc – Installation manual (MFL68026607 Rev.21) (MFL68026607 Rev.21_062126) , p. 277 official manufacturer document quote verified
Sensor fault
- [5] LG Therma V Monobloc – Installation manual (MFL68026607 Rev.21) (MFL68026607 Rev.21_062126) , p. 277 official manufacturer document quote verified
Resistance: 10 kΩ at 25
- [6] LG Therma V Monobloc – Installation manual (MFL68026607 Rev.21) (MFL68026607 Rev.21_062126) , p. 277 official manufacturer document quote verified
Resistance: 5 kΩ at 25
- [7] LG Therma V Monobloc – Installation manual (MFL68026607 Rev.21) (MFL68026607 Rev.21_062126) , p. 277 official manufacturer document quote verified
Voltage: 2.5 V DC at 25 centigrade (plugged) (for all sensors)
- [8] LG Therma V Monobloc – Installation manual (MFL68026607 Rev.21) (MFL68026607 Rev.21_062126) , p. 277 official manufacturer document quote verified
Refer resistance-temperature table to check in different temperature