Mitsubishi Electric · Heat pumps · Mitsubishi Electric Ecodan FTC7 controller (PUZ-WM/WZ, PUHZ-SW)
L3Circulation water temperature overheat protection
Name in the manufacturer's documentation (service manual): Circulation water temperature overheat protection
[1]
In plain words (editorial)
Circulation water overheat protection – the flow rate may be reduced. The manual says to check for water leakage, a blocked magnetic filter or strainer, and the circulation pump. The code may also show while the primary circuit is being filled.
When to call a service technician: Filter and pump checks are done by the installer.
✎ editorial – written from the cited sources, not a manufacturer statement. Status: draft.
For technicians
Possible causes (source text)
- Flow rate may be reduced[2]
Steps given by the manufacturer (source text)
Notes from the documentation
- Error code may display during filling of primary circuit, complete filling and reset error code[6]
⚠ Work on refrigerant circuits, mains electricity and PV DC wiring is for qualified technicians only.
The Polish page has more detail (plain-language explanation, safe checks, guides): Read in Polish →
Sources
Every statement has a footnote to the document and PDF page. “Quote verified” means the quote was found automatically in the text of that page.
- [1] Mitsubishi Electric Ecodan FTC7 PAC-IF081B-E / PAC-IF082B-E / PAC-IF083B-E – Installation Manual (DG79H200H02) , p. 33 official manufacturer document quote verified
L3 Circulation water temperature overheat protection
- [2] Mitsubishi Electric Ecodan FTC7 PAC-IF081B-E / PAC-IF082B-E / PAC-IF083B-E – Installation Manual (DG79H200H02) , p. 33 official manufacturer document quote verified
Flow rate may be reduced. Check for;
- [3] Mitsubishi Electric Ecodan FTC7 PAC-IF081B-E / PAC-IF082B-E / PAC-IF083B-E – Installation Manual (DG79H200H02) , p. 33 official manufacturer document quote verified
Water leakage
- [4] Mitsubishi Electric Ecodan FTC7 PAC-IF081B-E / PAC-IF082B-E / PAC-IF083B-E – Installation Manual (DG79H200H02) , p. 33 official manufacturer document quote verified
Magnetic filter / Strainer blockage
- [5] Mitsubishi Electric Ecodan FTC7 PAC-IF081B-E / PAC-IF082B-E / PAC-IF083B-E – Installation Manual (DG79H200H02) , p. 33 official manufacturer document quote verified
Water circulation pump function (Error code may display during filling
- [6] Mitsubishi Electric Ecodan FTC7 PAC-IF081B-E / PAC-IF082B-E / PAC-IF083B-E – Installation Manual (DG79H200H02) , p. 33 official manufacturer document quote verified
complete filling and reset error code