Mitsubishi Electric · Mitsubishi Electric Ecodan FTC7 controller (PUZ-WM/WZ, PUHZ-SW) · Troubleshooting
Ecodan: water flow and the magnetic filter – what the installer checks for L9, L3, L6, LP
Summary (editorial)
Flow-related codes often come from a restricted water circuit. The manual describes adjustments and checks that are done by the installer.
✎ editorial – written from the cited sources, not a manufacturer statement. Status: draft.
From the manufacturer's documentation (English source wording, with page)
- Adjust pump speed so that flow suits the outdoor unit (Table 3.4.1)[1]
- Flow sensor minimum default 5.0 L/min[2]
- Strainer/magnetic filter protects parts from iron particles and contamination[3]
- Water leakage, magnetic filter / strainer blockage, pump function[4]
- Pump valves may be hot[5]
- PUZ-WM85 10.8–24.4 L/min[6]
⚠ Work on refrigerant circuits, mains electricity and PV DC wiring is for qualified technicians only.
The Polish page has more detail (plain-language explanation, safe checks, guides): Read in Polish →
Sources
Every statement has a footnote to the document and PDF page. “Quote verified” means the quote was found automatically in the text of that page.
- [1] Mitsubishi Electric Ecodan FTC7 PAC-IF081B-E / PAC-IF082B-E / PAC-IF083B-E – Installation Manual (DG79H200H02) , p. 7 official manufacturer document quote verified
Adjust the pump speed setting so that the flow rate in the primary circuit is appropriate for the outdoor unit installed
- [2] Mitsubishi Electric Ecodan FTC7 PAC-IF081B-E / PAC-IF082B-E / PAC-IF083B-E – Installation Manual (DG79H200H02) , p. 7 official manufacturer document quote verified
default 5.0 L/min
- [3] Mitsubishi Electric Ecodan FTC7 PAC-IF081B-E / PAC-IF082B-E / PAC-IF083B-E – Installation Manual (DG79H200H02) , p. 7 official manufacturer document quote verified
Provide it as required to protect parts from damages caused by iron particles
- [4] Mitsubishi Electric Ecodan FTC7 PAC-IF081B-E / PAC-IF082B-E / PAC-IF083B-E – Installation Manual (DG79H200H02) , p. 33 official manufacturer document quote verified
Magnetic filter / Strainer blockage
- [5] Mitsubishi Electric Ecodan FTC7 PAC-IF081B-E / PAC-IF082B-E / PAC-IF083B-E – Installation Manual (DG79H200H02) , p. 33 official manufacturer document quote verified
Caution: The pump valves may be hot, please take care.
- [6] Mitsubishi Electric Ecodan FTC7 PAC-IF081B-E / PAC-IF082B-E / PAC-IF083B-E – Installation Manual (DG79H200H02) , p. 7 official manufacturer document quote verified
PUZ-WM85 10.8 - 24.4