Mitsubishi Electric · Heat pumps · Mitsubishi Electric Ecodan PUZ-WM outdoor unit (R32)
P6Freezing/overheating protection is working
Name in the manufacturer's documentation (service manual): Freezing/overheating protection is working
[1]
In plain words (editorial)
Freezing or overheating protection of the plate heat exchanger is active. The service manual lists reduced water flow (clogged filter, water leak), a faulty water pump, refrigerant shortage or the expansion valve.
When to call a service technician: Call the installer to check water flow and the circuit.
✎ editorial – written from the cited sources, not a manufacturer statement. Status: draft.
For technicians
Detection conditions (source text)
- Plate HEX Liquid temperature(TH34) or refrigerant saturation temperature is 10 seconds smaller than the threshold[2]
Possible causes (source text)
Steps given by the manufacturer (source text)
⚠ Work on refrigerant circuits, mains electricity and PV DC wiring is for qualified technicians only.
The Polish page has more detail (plain-language explanation, safe checks, guides): Read in Polish →
Sources
Every statement has a footnote to the document and PDF page. “Quote verified” means the quote was found automatically in the text of that page.
- [1] Mitsubishi Electric – Service Manual: Air to water heat pump units, outdoor unit PUZ-WM50VHA … PUZ-WM112YAA (OCH727 REVISED EDITION-A, 12/2023) (OCH727A (12/2023)) , p. 31 official manufacturer document quote verified
- [2] Mitsubishi Electric – Service Manual: Air to water heat pump units, outdoor unit PUZ-WM50VHA … PUZ-WM112YAA (OCH727 REVISED EDITION-A, 12/2023) (OCH727A (12/2023)) , p. 31 official manufacturer document quote verified
Plate HEX Liquid temperature(TH34) or refrigerant saturation temperature is 10 seconds smaller than the threshold
- [3] Mitsubishi Electric – Service Manual: Air to water heat pump units, outdoor unit PUZ-WM50VHA … PUZ-WM112YAA (OCH727 REVISED EDITION-A, 12/2023) (OCH727A (12/2023)) , p. 31 official manufacturer document quote verified
Reduced water flow · Clogged filter · Leakage of water
- [4] Mitsubishi Electric – Service Manual: Air to water heat pump units, outdoor unit PUZ-WM50VHA … PUZ-WM112YAA (OCH727 REVISED EDITION-A, 12/2023) (OCH727A (12/2023)) , p. 31 official manufacturer document quote verified
Defective water pump
- [5] Mitsubishi Electric – Service Manual: Air to water heat pump units, outdoor unit PUZ-WM50VHA … PUZ-WM112YAA (OCH727 REVISED EDITION-A, 12/2023) (OCH727A (12/2023)) , p. 31 official manufacturer document quote verified
Leakage or shortage of refrigerant
- [6] Mitsubishi Electric – Service Manual: Air to water heat pump units, outdoor unit PUZ-WM50VHA … PUZ-WM112YAA (OCH727 REVISED EDITION-A, 12/2023) (OCH727A (12/2023)) , p. 31 official manufacturer document quote verified
Malfunction of linear expansion valve
- [7] Mitsubishi Electric – Service Manual: Air to water heat pump units, outdoor unit PUZ-WM50VHA … PUZ-WM112YAA (OCH727 REVISED EDITION-A, 12/2023) (OCH727A (12/2023)) , p. 31 official manufacturer document quote verified
Check water piping
- [8] Mitsubishi Electric – Service Manual: Air to water heat pump units, outdoor unit PUZ-WM50VHA … PUZ-WM112YAA (OCH727 REVISED EDITION-A, 12/2023) (OCH727A (12/2023)) , p. 31 official manufacturer document quote verified
Check water pump
- [9] Mitsubishi Electric – Service Manual: Air to water heat pump units, outdoor unit PUZ-WM50VHA … PUZ-WM112YAA (OCH727 REVISED EDITION-A, 12/2023) (OCH727A (12/2023)) , p. 31 official manufacturer document quote verified
Check linear expansion valve