Mitsubishi Electric · Heat pumps · Mitsubishi Electric Ecodan PUZ-WM outdoor unit (R32)
U7Too low superheat due to low discharge temperature
Name in the manufacturer's documentation (service manual): Too low superheat due to low discharge temperature
[1]
In plain words (editorial)
Too low superheat due to low discharge temperature. The service manual names a disconnected or loose discharge thermistor (TH4) or its defective holder, or a problem with the linear expansion valve or its coil.
When to call a service technician: Contact your installer or a Mitsubishi Electric service technician.
✎ editorial – written from the cited sources, not a manufacturer statement. Status: draft.
For technicians
Detection conditions (source text)
- Abnormal if discharge superheat is continuously detected less than or equal to −15°C for 3 minutes[2]
Possible causes (source text)
Steps given by the manufacturer (source text)
⚠ Work on refrigerant circuits, mains electricity and PV DC wiring is for qualified technicians only.
The Polish page has more detail (plain-language explanation, safe checks, guides): Read in Polish →
Sources
Every statement has a footnote to the document and PDF page. “Quote verified” means the quote was found automatically in the text of that page.
- [1] Mitsubishi Electric – Service Manual: Air to water heat pump units, outdoor unit PUZ-WM50VHA … PUZ-WM112YAA (OCH727 REVISED EDITION-A, 12/2023) (OCH727A (12/2023)) , p. 26 official manufacturer document quote verified
- [2] Mitsubishi Electric – Service Manual: Air to water heat pump units, outdoor unit PUZ-WM50VHA … PUZ-WM112YAA (OCH727 REVISED EDITION-A, 12/2023) (OCH727A (12/2023)) , p. 26 official manufacturer document quote verified
abnormal if discharge superheat is
- [3] Mitsubishi Electric – Service Manual: Air to water heat pump units, outdoor unit PUZ-WM50VHA … PUZ-WM112YAA (OCH727 REVISED EDITION-A, 12/2023) (OCH727A (12/2023)) , p. 26 official manufacturer document quote verified
connection of discharge
- [4] Mitsubishi Electric – Service Manual: Air to water heat pump units, outdoor unit PUZ-WM50VHA … PUZ-WM112YAA (OCH727 REVISED EDITION-A, 12/2023) (OCH727A (12/2023)) , p. 26 official manufacturer document quote verified
defective holder of discharge
- [5] Mitsubishi Electric – Service Manual: Air to water heat pump units, outdoor unit PUZ-WM50VHA … PUZ-WM112YAA (OCH727 REVISED EDITION-A, 12/2023) (OCH727A (12/2023)) , p. 26 official manufacturer document quote verified
of linear expansion valve’s coil
- [6] Mitsubishi Electric – Service Manual: Air to water heat pump units, outdoor unit PUZ-WM50VHA … PUZ-WM112YAA (OCH727 REVISED EDITION-A, 12/2023) (OCH727A (12/2023)) , p. 26 official manufacturer document quote verified
5 defective linear expansion valve
- [7] Mitsubishi Electric – Service Manual: Air to water heat pump units, outdoor unit PUZ-WM50VHA … PUZ-WM112YAA (OCH727 REVISED EDITION-A, 12/2023) (OCH727A (12/2023)) , p. 26 official manufacturer document quote verified
check the installation conditions of
- [8] Mitsubishi Electric – Service Manual: Air to water heat pump units, outdoor unit PUZ-WM50VHA … PUZ-WM112YAA (OCH727 REVISED EDITION-A, 12/2023) (OCH727A (12/2023)) , p. 26 official manufacturer document quote verified
check the coil of linear expansion valve
- [9] Mitsubishi Electric – Service Manual: Air to water heat pump units, outdoor unit PUZ-WM50VHA … PUZ-WM112YAA (OCH727 REVISED EDITION-A, 12/2023) (OCH727A (12/2023)) , p. 26 official manufacturer document quote verified
check the connection or contact of lev-a and
- [10] Mitsubishi Electric – Service Manual: Air to water heat pump units, outdoor unit PUZ-WM50VHA … PUZ-WM112YAA (OCH727 REVISED EDITION-A, 12/2023) (OCH727A (12/2023)) , p. 26 official manufacturer document quote verified
5 check linear expansion valve