Panasonic · Heat pumps · Panasonic Aquarea Monobloc, generation H
H98Outdoor high pressure overload protection
Name in the manufacturer's documentation (service manual): Outdoor high pressure overload protection
[1]
In plain words (editorial)
In heating mode the refrigerant pressure is too high and the overload protection stopped the unit. The service manual lists water-side causes (water pump, water flow or leakage) among others – see the technical section below.
When to call a service technician: If the code repeats, call the installer.
✎ editorial – written from the cited sources, not a manufacturer statement. Status: draft.
For technicians
Detection conditions (source text)
- During operation of heating, when pressure 4.0 MPa and above is detected by outdoor high pressure sensor.[2]
Possible causes (source text)
⚠ Work on refrigerant circuits, mains electricity and PV DC wiring is for qualified technicians only.
The Polish page has more detail (plain-language explanation, safe checks, guides): Read in Polish →
Sources
Every statement has a footnote to the document and PDF page. “Quote verified” means the quote was found automatically in the text of that page.
- [1] Service Manual – Mono Bloc Unit WH-MDC05H3E5 / 07 / 09 (PAPAMY1709003CE) , p. 145 official manufacturer document quote verified
H98 Outdoor high pressure overload protection
- [2] Service Manual – Mono Bloc Unit WH-MDC05H3E5 / 07 / 09 (PAPAMY1709003CE) , p. 171 official manufacturer document quote verified
During operation of heating, when pressure 4.0 MPa and above is detected by outdoor high pressure sensor.
- [3] Service Manual – Mono Bloc Unit WH-MDC05H3E5 / 07 / 09 (PAPAMY1709003CE) , p. 171 official manufacturer document quote verified
Faulty water pump.
- [4] Service Manual – Mono Bloc Unit WH-MDC05H3E5 / 07 / 09 (PAPAMY1709003CE) , p. 171 official manufacturer document quote verified
Insufficient water flow rate in system.
- [5] Service Manual – Mono Bloc Unit WH-MDC05H3E5 / 07 / 09 (PAPAMY1709003CE) , p. 171 official manufacturer document quote verified
Water leak in system.
- [6] Service Manual – Mono Bloc Unit WH-MDC05H3E5 / 07 / 09 (PAPAMY1709003CE) , p. 171 official manufacturer document quote verified
2/3 way closed.
- [7] Service Manual – Mono Bloc Unit WH-MDC05H3E5 / 07 / 09 (PAPAMY1709003CE) , p. 171 official manufacturer document quote verified
Clogged expansion valve or strainer.
- [8] Service Manual – Mono Bloc Unit WH-MDC05H3E5 / 07 / 09 (PAPAMY1709003CE) , p. 171 official manufacturer document quote verified
Excessive refrigerant.
- [9] Service Manual – Mono Bloc Unit WH-MDC05H3E5 / 07 / 09 (PAPAMY1709003CE) , p. 171 official manufacturer document quote verified
Faulty outdoor high pressure sensor.
- [10] Service Manual – Mono Bloc Unit WH-MDC05H3E5 / 07 / 09 (PAPAMY1709003CE) , p. 171 official manufacturer document quote verified
Faulty outdoor unit PCB (main).