H27Service valve error

Name in the manufacturer's documentation (service manual): Service valve error[1]

This page only quotes the original English documentation. A plain-language explanation has not been written yet, so the page is not indexed by search engines.

The Polish page has more detail (plain-language explanation, safe checks, guides): Read in Polish →

Sources

Every statement has a footnote to the document and PDF page. “Quote verified” means the quote was found automatically in the text of that page.

  1. [1] Service Manual – WH-SDC03/05/07/09H3E5-1 + WH-UD03/05/07/09HE5-1 (PAPAMY1703036CE) , p. 153 manufacturer document – copy from a distributor quote verified H27 Service valve error
  2. [2] Service Manual – WH-SDC03/05/07/09H3E5-1 + WH-UD03/05/07/09HE5-1 (PAPAMY1703036CE) , p. 159 manufacturer document – copy from a distributor quote verified During cooling operation, when:- [a] Indoor refrigerant pipe temperature at compressor startup - present indoor refrigerant pipe temperature < 2°C [b] Present high pressure - high pressure at compressor startup < 5kg/cm2…
  3. [3] Service Manual – WH-SDC03/05/07/09H3E5-1 + WH-UD03/05/07/09HE5-1 (PAPAMY1703036CE) , p. 159 manufacturer document – copy from a distributor quote verified Continue for 5 minutes.
  4. [4] Service Manual – WH-SDC03/05/07/09H3E5-1 + WH-UD03/05/07/09HE5-1 (PAPAMY1703036CE) , p. 159 manufacturer document – copy from a distributor quote verified 3 way valves closed.
  5. [5] Service Manual – WH-SDC03/05/07/09H3E5-1 + WH-UD03/05/07/09HE5-1 (PAPAMY1703036CE) , p. 159 manufacturer document – copy from a distributor quote verified Faulty high pressure sensor.
  6. [6] Service Manual – WH-SDC03/05/07/09H3E5-1 + WH-UD03/05/07/09HE5-1 (PAPAMY1703036CE) , p. 159 manufacturer document – copy from a distributor quote verified Faulty indoor refrigerant pipe temperature sensor
  7. [7] Service Manual – WH-SDC03/05/07/09H3E5-1 + WH-UD03/05/07/09HE5-1 (PAPAMY1703036CE) , p. 159 manufacturer document – copy from a distributor quote verified Faulty outdoor unit PCB (main).
  8. [8] Service Manual – WH-SDC03/05/07/09H3E5-1 + WH-UD03/05/07/09HE5-1 (PAPAMY1703036CE) , p. 160 manufacturer document – copy from a distributor quote verified always switch off the power before remove and connect the component.