Panasonic · Heat pumps · Panasonic Aquarea Monobloc, generation J (R32)
H62Water flow switch abnormality
Name in the manufacturer's documentation (service manual): Water flow switch abnormality
[1]
In plain words (editorial)
The water flow switch does not detect enough water flow and the unit stops; according to the service manual, after 60 seconds of low flow the water pump and compressor switch off and the OFF/ON LED blinks. Even after a reset the error returns if the cause is not repaired.
When to call a service technician: Call the installer: the water pump and the water circuit (flow, air, filter) must be checked.
✎ editorial – written from the cited sources, not a manufacturer statement. Status: draft.
For technicians
Detection conditions (source text)
Possible causes (source text)
- Faulty water pump.[5]
What the device does (source text)
- Low flow 60 s continuously -> water pump and compressor OFF permanently, OFF/ON LED blinks (H62)[6]
Notes from the documentation
- Even after reset by power OFF or ERROR RESET, if not repaired the error returns[7]
⚠ Work on refrigerant circuits, mains electricity and PV DC wiring is for qualified technicians only.
The Polish page has more detail (plain-language explanation, safe checks, guides): Read in Polish →
Sources
Every statement has a footnote to the document and PDF page. “Quote verified” means the quote was found automatically in the text of that page.
- [1] Service Manual – Mono Bloc Unit WH-MDC05J3E5 / WH-MDC07J3E5 / WH-MDC09J3E5 (PAPAMY2003034CE) , p. 164 manufacturer document – copy from a distributor quote verified
Water flow switch abnormality
- [2] Service Manual – Mono Bloc Unit WH-MDC05J3E5 / WH-MDC07J3E5 / WH-MDC09J3E5 (PAPAMY2003034CE) , p. 178 manufacturer document – copy from a distributor quote verified
the water flow detected by the indoor water flow switch is used to
- [3] Service Manual – Mono Bloc Unit WH-MDC05J3E5 / WH-MDC07J3E5 / WH-MDC09J3E5 (PAPAMY2003034CE) , p. 178 manufacturer document – copy from a distributor quote verified
Continue for 10 seconds (but no judgment for 9 minutes after compressor startup/restart)
- [4] Service Manual – Mono Bloc Unit WH-MDC05J3E5 / WH-MDC07J3E5 / WH-MDC09J3E5 (PAPAMY2003034CE) , p. 164 manufacturer document – copy from a distributor quote verified
Water flow switch abnormality Continue for 1 min.
- [5] Service Manual – Mono Bloc Unit WH-MDC05J3E5 / WH-MDC07J3E5 / WH-MDC09J3E5 (PAPAMY2003034CE) , p. 178 manufacturer document – copy from a distributor quote verified
Faulty water pump.
- [6] Service Manual – Mono Bloc Unit WH-MDC05J3E5 / WH-MDC07J3E5 / WH-MDC09J3E5 (PAPAMY2003034CE) , p. 116 manufacturer document – copy from a distributor quote verified
If water flow level is detected low continuously 60 seconds, the water pump and the compressor will be OFF permanently
- [7] Service Manual – Mono Bloc Unit WH-MDC05J3E5 / WH-MDC07J3E5 / WH-MDC09J3E5 (PAPAMY2003034CE) , p. 162 manufacturer document – copy from a distributor quote verified
Even error code is reset by turning OFF power supply or by selecting ERROR RESET