H90Indoor/outdoor abnormal communication
Name in the manufacturer's documentation (service manual): Indoor/outdoor abnormal communication
[1]
In plain words (editorial)
The indoor and outdoor units cannot communicate properly – wiring between them or one of the PCBs.
When to call a service technician: The connection wiring is checked by the installer.
✎ editorial – written from the cited sources, not a manufacturer statement. Status: draft.
For technicians
Detection conditions (source text)
Possible causes (source text)
- Faulty outdoor unit PCB (main).[4]
- Faulty indoor unit PCB (main).[5]
- Indoor-outdoor signal transmission error due to wrong wiring.[6]
- Indoor-outdoor signal transmission error due to breaking of wire in the connection wires between the indoor and outdoor units.[7]
- Indoor-outdoor signal transmission error due to disturbed power supply waveform.[8]
⚠ Work on refrigerant circuits, mains electricity and PV DC wiring is for qualified technicians only.
The Polish page has more detail (plain-language explanation, safe checks, guides): Read in Polish →
Sources
Every statement has a footnote to the document and PDF page. “Quote verified” means the quote was found automatically in the text of that page.
- [1] Service Manual – Mono Bloc Unit WH-MDC05J3E5 / WH-MDC07J3E5 / WH-MDC09J3E5 (PAPAMY2003034CE) , p. 164 manufacturer document – copy from a distributor quote verified
h90 indoor/outdoor abnormal communication > 1 min after starting operation
- [2] Service Manual – Mono Bloc Unit WH-MDC05J3E5 / WH-MDC07J3E5 / WH-MDC09J3E5 (PAPAMY2003034CE) , p. 187 manufacturer document – copy from a distributor quote verified
the data received from outdoor unit in indoor unit signal transmission is checked whether it is normal
- [3] Service Manual – Mono Bloc Unit WH-MDC05J3E5 / WH-MDC07J3E5 / WH-MDC09J3E5 (PAPAMY2003034CE) , p. 187 manufacturer document – copy from a distributor quote verified
abnormality judgment: continue for 1 minute after operation.
- [4] Service Manual – Mono Bloc Unit WH-MDC05J3E5 / WH-MDC07J3E5 / WH-MDC09J3E5 (PAPAMY2003034CE) , p. 187 manufacturer document – copy from a distributor quote verified
Faulty outdoor unit PCB (main).
- [5] Service Manual – Mono Bloc Unit WH-MDC05J3E5 / WH-MDC07J3E5 / WH-MDC09J3E5 (PAPAMY2003034CE) , p. 187 manufacturer document – copy from a distributor quote verified
Faulty indoor unit PCB (main).
- [6] Service Manual – Mono Bloc Unit WH-MDC05J3E5 / WH-MDC07J3E5 / WH-MDC09J3E5 (PAPAMY2003034CE) , p. 187 manufacturer document – copy from a distributor quote verified
Indoor-outdoor signal transmission error due to wrong wiring.
- [7] Service Manual – Mono Bloc Unit WH-MDC05J3E5 / WH-MDC07J3E5 / WH-MDC09J3E5 (PAPAMY2003034CE) , p. 187 manufacturer document – copy from a distributor quote verified
Indoor-outdoor signal transmission error due to breaking of wire in the connection wires between the indoor and outdoor units.
- [8] Service Manual – Mono Bloc Unit WH-MDC05J3E5 / WH-MDC07J3E5 / WH-MDC09J3E5 (PAPAMY2003034CE) , p. 187 manufacturer document – copy from a distributor quote verified
Indoor-outdoor signal transmission error due to disturbed power supply waveform.