Panasonic · Heat pumps · Panasonic Aquarea Monobloc, generation J (R32)
H99Indoor heat exchanger freeze prevention
Name in the manufacturer's documentation (service manual): Indoor heat exchanger freeze prevention
[1]
In plain words (editorial)
In cooling mode the indoor heat exchanger got too cold and could freeze (freeze prevention), usually because of too little water flow.
When to call a service technician: If the code repeats, call the installer.
✎ editorial – written from the cited sources, not a manufacturer statement. Status: draft.
For technicians
Detection conditions (source text)
Possible causes (source text)
⚠ Work on refrigerant circuits, mains electricity and PV DC wiring is for qualified technicians only.
The Polish page has more detail (plain-language explanation, safe checks, guides): Read in Polish →
Sources
Every statement has a footnote to the document and PDF page. “Quote verified” means the quote was found automatically in the text of that page.
- [1] Service Manual – Mono Bloc Unit WH-MDC05J3E5 / WH-MDC07J3E5 / WH-MDC09J3E5 (PAPAMY2003034CE) , p. 164 manufacturer document – copy from a distributor quote verified
h99 indoor heat exchanger freeze prevention
- [2] Service Manual – Mono Bloc Unit WH-MDC05J3E5 / WH-MDC07J3E5 / WH-MDC09J3E5 (PAPAMY2003034CE) , p. 191 manufacturer document – copy from a distributor quote verified
during anti-freezing control in cooling operation, when the indoor refrigerant liquid temperature < 0°c
- [3] Service Manual – Mono Bloc Unit WH-MDC05J3E5 / WH-MDC07J3E5 / WH-MDC09J3E5 (PAPAMY2003034CE) , p. 164 manufacturer document – copy from a distributor quote verified
4 times occurrence within 20
- [4] Service Manual – Mono Bloc Unit WH-MDC05J3E5 / WH-MDC07J3E5 / WH-MDC09J3E5 (PAPAMY2003034CE) , p. 191 manufacturer document – copy from a distributor quote verified
Faulty water pump.
- [5] Service Manual – Mono Bloc Unit WH-MDC05J3E5 / WH-MDC07J3E5 / WH-MDC09J3E5 (PAPAMY2003034CE) , p. 191 manufacturer document – copy from a distributor quote verified
Insufficient water flow rate in system.
- [6] Service Manual – Mono Bloc Unit WH-MDC05J3E5 / WH-MDC07J3E5 / WH-MDC09J3E5 (PAPAMY2003034CE) , p. 191 manufacturer document – copy from a distributor quote verified
Water leak in system.
- [7] Service Manual – Mono Bloc Unit WH-MDC05J3E5 / WH-MDC07J3E5 / WH-MDC09J3E5 (PAPAMY2003034CE) , p. 191 manufacturer document – copy from a distributor quote verified
2 way valve partially closed.
- [8] Service Manual – Mono Bloc Unit WH-MDC05J3E5 / WH-MDC07J3E5 / WH-MDC09J3E5 (PAPAMY2003034CE) , p. 191 manufacturer document – copy from a distributor quote verified
Clogged expansion valve or strainer.
- [9] Service Manual – Mono Bloc Unit WH-MDC05J3E5 / WH-MDC07J3E5 / WH-MDC09J3E5 (PAPAMY2003034CE) , p. 191 manufacturer document – copy from a distributor quote verified
Refrigerant shortage (refrigerant leakage).
- [10] Service Manual – Mono Bloc Unit WH-MDC05J3E5 / WH-MDC07J3E5 / WH-MDC09J3E5 (PAPAMY2003034CE) , p. 191 manufacturer document – copy from a distributor quote verified
Faulty indoor refrigerant liquid temperature sensor.
- [11] Service Manual – Mono Bloc Unit WH-MDC05J3E5 / WH-MDC07J3E5 / WH-MDC09J3E5 (PAPAMY2003034CE) , p. 191 manufacturer document – copy from a distributor quote verified
Faulty indoor unit PCB (main).