Panasonic · Heat pumps · Panasonic Aquarea Bi-bloc (split), generation L (R290)
H90Indoor/outdoor abnormal communication
Name in the manufacturer's documentation (service manual): Indoor/outdoor abnormal communication
[1]
In plain words (editorial)
The indoor and outdoor units cannot communicate properly – wiring between them or one of the PCBs.
When to call a service technician: The connection wiring is checked by the installer.
✎ editorial – written from the cited sources, not a manufacturer statement. Status: draft.
For technicians
Detection conditions (source text)
Possible causes (source text)
- Faulty outdoor unit PCB (main).[4]
- Faulty indoor unit PCB (main).[5]
- Indoor-outdoor signal transmission error due to wrong wiring.[6]
- Indoor-outdoor signal transmission error due to breaking of wire in the connection wires between the indoor and outdoor units.[7]
- Indoor-outdoor signal transmission error due to disturbed power supply waveform.[8]
Safety notes from the documentation
- Always switch off the power before remove and connect the component.[9]
⚠ Work on refrigerant circuits, mains electricity and PV DC wiring is for qualified technicians only.
The Polish page has more detail (plain-language explanation, safe checks, guides): Read in Polish →
Sources
Every statement has a footnote to the document and PDF page. “Quote verified” means the quote was found automatically in the text of that page.
- [1] Service Manual – WH-SDC0509L3E5 / L6E5 + WH-WDG05/07/09LE5 (R290) (PAPAMY2307068CE) , p. 189 manufacturer document – copy from a distributor quote verified
H90 Indoor/outdoor abnormal communication
- [2] Service Manual – WH-SDC0509L3E5 / L6E5 + WH-WDG05/07/09LE5 (R290) (PAPAMY2307068CE) , p. 214 manufacturer document – copy from a distributor quote verified
During operation of cooling and heating, the data received from outdoor unit in indoor unit signal transmission is checked whether it is normal.
- [3] Service Manual – WH-SDC0509L3E5 / L6E5 + WH-WDG05/07/09LE5 (R290) (PAPAMY2307068CE) , p. 214 manufacturer document – copy from a distributor quote verified
Continue for 1 minute after operation.
- [4] Service Manual – WH-SDC0509L3E5 / L6E5 + WH-WDG05/07/09LE5 (R290) (PAPAMY2307068CE) , p. 214 manufacturer document – copy from a distributor quote verified
Faulty outdoor unit PCB (main).
- [5] Service Manual – WH-SDC0509L3E5 / L6E5 + WH-WDG05/07/09LE5 (R290) (PAPAMY2307068CE) , p. 214 manufacturer document – copy from a distributor quote verified
Faulty indoor unit PCB (main).
- [6] Service Manual – WH-SDC0509L3E5 / L6E5 + WH-WDG05/07/09LE5 (R290) (PAPAMY2307068CE) , p. 214 manufacturer document – copy from a distributor quote verified
Indoor-outdoor signal transmission error due to wrong wiring.
- [7] Service Manual – WH-SDC0509L3E5 / L6E5 + WH-WDG05/07/09LE5 (R290) (PAPAMY2307068CE) , p. 214 manufacturer document – copy from a distributor quote verified
Indoor-outdoor signal transmission error due to breaking of wire in the connection wires between the indoor and outdoor units.
- [8] Service Manual – WH-SDC0509L3E5 / L6E5 + WH-WDG05/07/09LE5 (R290) (PAPAMY2307068CE) , p. 214 manufacturer document – copy from a distributor quote verified
Indoor-outdoor signal transmission error due to disturbed power supply waveform.
- [9] Service Manual – WH-SDC0509L3E5 / L6E5 + WH-WDG05/07/09LE5 (R290) (PAPAMY2307068CE) , p. 214 manufacturer document – copy from a distributor quote verified
always switch off the power before remove and connect the component.