Panasonic · Heat pumps · Panasonic Aquarea T-CAP Monobloc, generation J (R32)
H62Water flow switch abnormality
Name in the manufacturer's documentation (service manual): Water flow switch abnormality
[1]
In plain words (editorial)
The water flow switch does not detect enough water flow and the unit has stopped. The service manual lists the water pump, a water leak, a connector, the flow switch and the PCB as causes.
When to call a service technician: If the code returns after a restart, call the installer.
✎ editorial – written from the cited sources, not a manufacturer statement. Status: draft.
For technicians
Detection conditions (source text)
Possible causes (source text)
What the device does (source text)
- No error judgement for 70 s after start; low flow 60 s continuously -> water pump and compressor OFF permanently, OFF/ON LED blinks (H62)[9]
Safety notes from the documentation
- Always switch off the power before remove and connect the component.[10]
⚠ Work on refrigerant circuits, mains electricity and PV DC wiring is for qualified technicians only.
The Polish page has more detail (plain-language explanation, safe checks, guides): Read in Polish →
Sources
Every statement has a footnote to the document and PDF page. “Quote verified” means the quote was found automatically in the text of that page.
- [1] Service Manual – Mono Bloc Unit WH-MXC09J3E5 / WH-MXC12J6E5 (Aquarea T-CAP, R32) (PAPAMY2101001CE) , p. 164 official manufacturer document quote verified
H62 Water flow switch abnormality
- [2] Service Manual – Mono Bloc Unit WH-MXC09J3E5 / WH-MXC12J6E5 (Aquarea T-CAP, R32) (PAPAMY2101001CE) , p. 178 official manufacturer document quote verified
the water flow detected by the indoor water flow switch is used to
- [3] Service Manual – Mono Bloc Unit WH-MXC09J3E5 / WH-MXC12J6E5 (Aquarea T-CAP, R32) (PAPAMY2101001CE) , p. 178 official manufacturer document quote verified
Continue for 10 seconds (but no judgment for 9 minutes after compressor startup/restart)
- [4] Service Manual – Mono Bloc Unit WH-MXC09J3E5 / WH-MXC12J6E5 (Aquarea T-CAP, R32) (PAPAMY2101001CE) , p. 178 official manufacturer document quote verified
Faulty water pump.
- [5] Service Manual – Mono Bloc Unit WH-MXC09J3E5 / WH-MXC12J6E5 (Aquarea T-CAP, R32) (PAPAMY2101001CE) , p. 178 official manufacturer document quote verified
Water leak in system.
- [6] Service Manual – Mono Bloc Unit WH-MXC09J3E5 / WH-MXC12J6E5 (Aquarea T-CAP, R32) (PAPAMY2101001CE) , p. 178 official manufacturer document quote verified
Faulty connector connection.
- [7] Service Manual – Mono Bloc Unit WH-MXC09J3E5 / WH-MXC12J6E5 (Aquarea T-CAP, R32) (PAPAMY2101001CE) , p. 178 official manufacturer document quote verified
Faulty water flow switch.
- [8] Service Manual – Mono Bloc Unit WH-MXC09J3E5 / WH-MXC12J6E5 (Aquarea T-CAP, R32) (PAPAMY2101001CE) , p. 178 official manufacturer document quote verified
Faulty indoor unit PCB (main).
- [9] Service Manual – Mono Bloc Unit WH-MXC09J3E5 / WH-MXC12J6E5 (Aquarea T-CAP, R32) (PAPAMY2101001CE) , p. 117 official manufacturer document quote verified
detected low continuously 60 seconds, the water pump and the compressor will be OFF permanently
- [10] Service Manual – Mono Bloc Unit WH-MXC09J3E5 / WH-MXC12J6E5 (Aquarea T-CAP, R32) (PAPAMY2101001CE) , p. 197 official manufacturer document quote verified
always switch off the power before remove and connect the component.