Vaillant · Heat pumps · Vaillant aroTHERM plus with uniTOWER plus
S.276Building circuit: Lockout contact S20 open
Name in the manufacturer's documentation (service manual): Building circuit: Lockout contact S20 open
[1]
In plain words (editorial)
The lockout contact S20 on the heat pump's main PCB is open – the manual names an incorrect limit thermostat setting or a flow temperature sensor reading too low. Its fix concerns the maximum flow temperature, the limit thermostat set value and the sensor values.
When to call a service technician: Ask a heating engineer to check the settings.
✎ editorial – written from the cited sources, not a manufacturer statement. Status: draft.
For technicians
Steps given by the manufacturer (source text)
Notes from the documentation
- Contact S20 is open at the heat pump's main PCB. Incorrect limit thermostat setting. Flow temperature sensor (heat pump, gas-fired boiler, system sensor) measures values that deviate downwards. Adjust the maximum flow temperature for the direct heating circuit via the system control (observe the upper switch-off threshold for the boilers). Adjust the set value for the limit thermostat. Check the sensor values[5][6]
⚠ Work on refrigerant circuits, mains electricity and PV DC wiring is for qualified technicians only.
The Polish page has more detail (plain-language explanation, safe checks, guides): Read in Polish →
Sources
Every statement has a footnote to the document and PDF page. “Quote verified” means the quote was found automatically in the text of that page.
- [1] Vaillant uniTOWER plus VIH QW 190/6 E – Operating, installation and maintenance instructions (0020291525_05) (0020291525_05) , p. 57 official manufacturer document quote verified
S.276 Building circuit: Lock
- [2] Vaillant uniTOWER plus VIH QW 190/6 E – Operating, installation and maintenance instructions (0020291525_05) (0020291525_05) , p. 57 official manufacturer document quote verified
Adjust the maximum flow temperature for the direct heating circuit via the system control
- [3] Vaillant uniTOWER plus VIH QW 190/6 E – Operating, installation and maintenance instructions (0020291525_05) (0020291525_05) , p. 57 official manufacturer document quote verified
Adjust the set value for the limit thermostat
- [4] Vaillant uniTOWER plus VIH QW 190/6 E – Operating, installation and maintenance instructions (0020291525_05) (0020291525_05) , p. 57 official manufacturer document quote verified
Check the sensor values
- [5] Vaillant uniTOWER plus VIH QW 190/6 E – Operating, installation and maintenance instructions (0020291525_05) (0020291525_05) , p. 57 official manufacturer document quote verified
Contact S20 is open at the heat pump's main PCB. Incorrect
- [6] Vaillant uniTOWER plus VIH QW 190/6 E – Operating, installation and maintenance instructions (0020291525_05) (0020291525_05) , p. 57 official manufacturer document quote verified
Contact S20 is open at the heat pump's main PCB