Viessmann · Heat pumps · Viessmann Vitocal 250-A (One Base, monobloc)
F.13Lead break, outside temperature sensor
Name in the manufacturer's documentation (service manual): Lead break, outside temperature sensor
[1]
In plain words (editorial)
Lead break of the outside temperature sensor (open circuit). Until it is fixed, an outside temperature value of 0 °C is used to calculate the flow temperature.
When to call a service technician: Contact your heating contractor or Viessmann technical service.
✎ editorial – written from the cited sources, not a manufacturer statement. Status: draft.
For technicians
Steps given by the manufacturer (source text)
What the device does (source text)
- An outside temperature value of 0 °C is used to calculate the set flow temperature.[6]
⚠ Work on refrigerant circuits, mains electricity and PV DC wiring is for qualified technicians only.
The Polish page has more detail (plain-language explanation, safe checks, guides): Read in Polish →
Sources
Every statement has a footnote to the document and PDF page. “Quote verified” means the quote was found automatically in the text of that page.
- [1] Viessmann – Service instructions: System configuration and diagnosis for heat pumps with Viessmann One Base (6194799 GB, 3/2022) (6194799 GB (3/2022)) , p. 51 manufacturer document – copy from a distributor quote verified
F.13
- [2] Viessmann – Service instructions: System configuration and diagnosis for heat pumps with Viessmann One Base (6194799 GB, 3/2022) (6194799 GB (3/2022)) , p. 51 manufacturer document – copy from a distributor quote verified
Check resistance value (NTC 10 kΩ)
- [3] Viessmann – Service instructions: System configuration and diagnosis for heat pumps with Viessmann One Base (6194799 GB, 3/2022) (6194799 GB (3/2022)) , p. 51 manufacturer document – copy from a distributor quote verified
Replace sensor if necessary
- [4] Viessmann – Service instructions: System configuration and diagnosis for heat pumps with Viessmann One Base (6194799 GB, 3/2022) (6194799 GB (3/2022)) , p. 51 manufacturer document – copy from a distributor quote verified
Wall mounted indoor unit: Connection on the underside of the appliance to 6-pole
- [5] Viessmann – Service instructions: System configuration and diagnosis for heat pumps with Viessmann One Base (6194799 GB, 3/2022) (6194799 GB (3/2022)) , p. 51 manufacturer document – copy from a distributor quote verified
Floorstanding indoor unit: Connection at luster terminals for sensors, terminal 5 and 6
- [6] Viessmann – Service instructions: System configuration and diagnosis for heat pumps with Viessmann One Base (6194799 GB, 3/2022) (6194799 GB (3/2022)) , p. 51 manufacturer document – copy from a distributor quote verified
An outside temperature value of 0 °C is used to calculate the set flow temperature