F.543Short circuit, flow temperature sensor, heating/cooling circuit 1 with mixer
Name in the manufacturer's documentation (service manual): Short circuit, flow temperature sensor, heating/cooling circuit 1 with mixer
[1]
This page only quotes the original English documentation. A plain-language explanation has not been written yet, so the page is not indexed by search engines.
For technicians
Steps given by the manufacturer (source text)
- Check the settings in the commissioning assistant.[2]
- Adjust settings if required.[3]
- Check setting of rotary switch S1 on ADIO electronics module.[4]
- Check flow temperature sensor in heating/cooling circuit 1.[5]
- Check resistance value (NTC 10 kΩ) at the sensor input on ADIO electronics module.[6]
- Replace sensor if necessary.[7]
What the device does (source text)
- Mixer closes. Heating circuit pump is operational.[8]
⚠ Work on refrigerant circuits, mains electricity and PV DC wiring is for qualified technicians only.
The Polish page has more detail (plain-language explanation, safe checks, guides): Read in Polish →
Sources
Every statement has a footnote to the document and PDF page. “Quote verified” means the quote was found automatically in the text of that page.
- [1] Viessmann – Service instructions: System configuration and diagnosis for heat pumps with Viessmann One Base (6194799 GB, 3/2022) (6194799 GB (3/2022)) , p. 56 manufacturer document – copy from a distributor quote verified
F.543
- [2] Viessmann – Service instructions: System configuration and diagnosis for heat pumps with Viessmann One Base (6194799 GB, 3/2022) (6194799 GB (3/2022)) , p. 56 manufacturer document – copy from a distributor quote verified
Check the settings in the
- [3] Viessmann – Service instructions: System configuration and diagnosis for heat pumps with Viessmann One Base (6194799 GB, 3/2022) (6194799 GB (3/2022)) , p. 56 manufacturer document – copy from a distributor quote verified
Adjust set- tings if required
- [4] Viessmann – Service instructions: System configuration and diagnosis for heat pumps with Viessmann One Base (6194799 GB, 3/2022) (6194799 GB (3/2022)) , p. 56 manufacturer document – copy from a distributor quote verified
Check setting of rotary switch S1 on ADIO electronics module
- [5] Viessmann – Service instructions: System configuration and diagnosis for heat pumps with Viessmann One Base (6194799 GB, 3/2022) (6194799 GB (3/2022)) , p. 56 manufacturer document – copy from a distributor quote verified
Check flow temperature sensor in heating/cooling circuit 1
- [6] Viessmann – Service instructions: System configuration and diagnosis for heat pumps with Viessmann One Base (6194799 GB, 3/2022) (6194799 GB (3/2022)) , p. 56 manufacturer document – copy from a distributor quote verified
Check resistance value (NTC 10 kΩ) at the sensor input on ADIO electronics module
- [7] Viessmann – Service instructions: System configuration and diagnosis for heat pumps with Viessmann One Base (6194799 GB, 3/2022) (6194799 GB (3/2022)) , p. 56 manufacturer document – copy from a distributor quote verified
Re- place sensor if necessary
- [8] Viessmann – Service instructions: System configuration and diagnosis for heat pumps with Viessmann One Base (6194799 GB, 3/2022) (6194799 GB (3/2022)) , p. 56 manufacturer document – copy from a distributor quote verified
Mixer closes. Heating circuit pump is operational