F.74Hydraulic system pressure too low
Name in the manufacturer's documentation (service manual): Hydraulic system pressure too low
[1]
In plain words (editorial)
The hydraulic system pressure is too low and the heat pump is switched off. The manual's first steps: top up with water and vent the system; if it repeats, the pressure sensor, the expansion vessel pre-charge and the pressure settings should be checked.
When to call a service technician: If the fault occurs repeatedly, contact your heating contractor.
✎ editorial – written from the cited sources, not a manufacturer statement. Status: draft.
For technicians
Steps given by the manufacturer (source text)
What the device does (source text)
- The heat pump is switched off[6]
⚠ Work on refrigerant circuits, mains electricity and PV DC wiring is for qualified technicians only.
The Polish page has more detail (plain-language explanation, safe checks, guides): Read in Polish →
Sources
Every statement has a footnote to the document and PDF page. “Quote verified” means the quote was found automatically in the text of that page.
- [1] Viessmann – Service instructions: System configuration and diagnosis for heat pumps with Viessmann One Base (6194799 GB, 3/2022) (6194799 GB (3/2022)) , p. 51 manufacturer document – copy from a distributor quote verified
Hydraulic system pressure too low
- [2] Viessmann – Service instructions: System configuration and diagnosis for heat pumps with Viessmann One Base (6194799 GB, 3/2022) (6194799 GB (3/2022)) , p. 51 manufacturer document – copy from a distributor quote verified
Top up with water. Vent the system.
- [3] Viessmann – Service instructions: System configuration and diagnosis for heat pumps with Viessmann One Base (6194799 GB, 3/2022) (6194799 GB (3/2022)) , p. 51 manufacturer document – copy from a distributor quote verified
Check system pressure sensor with external pressure gauge.
- [4] Viessmann – Service instructions: System configuration and diagnosis for heat pumps with Viessmann One Base (6194799 GB, 3/2022) (6194799 GB (3/2022)) , p. 51 manufacturer document – copy from a distributor quote verified
Check the pre-charge pressure of the expansion vessel.
- [5] Viessmann – Service instructions: System configuration and diagnosis for heat pumps with Viessmann One Base (6194799 GB, 3/2022) (6194799 GB (3/2022)) , p. 51 manufacturer document – copy from a distributor quote verified
Check settings for set system pressure and range.
- [6] Viessmann – Service instructions: System configuration and diagnosis for heat pumps with Viessmann One Base (6194799 GB, 3/2022) (6194799 GB (3/2022)) , p. 51 manufacturer document – copy from a distributor quote verified
The heat pump is switched off.