Daikin · Heat pumps · Daikin Altherma 3 R F (split heat pump, R32)

FA-00OU: Abnormal high pressure, actuation of HPS

Name in the manufacturer's documentation (service manual): OU: Abnormal high pressure, actuation of HPS[1]

In plain words (editorial)

Abnormally high pressure – the high pressure switch tripped. The manual names a dirty outdoor heat exchanger, too little air flow because the required space around the outdoor unit is not met, an outdoor temperature outside the operation range, refrigerant circuit problems or faulty components.

When to call a service technician: Keep the outdoor unit clean and unobstructed; if the code repeats, contact your installer.

✎ editorial – written from the cited sources, not a manufacturer statement. Status: draft.

The Polish page has more detail (plain-language explanation, safe checks, guides): Read in Polish →

Sources

Every statement has a footnote to the document and PDF page. “Quote verified” means the quote was found automatically in the text of that page.

  1. [1] Daikin Altherma 3 R F – ERGA04~08E + EHVH/X04+08S18+23E – Installer reference guide (4P629086-1D (2024.04)) , p. 254 official manufacturer document quote verified FA-00 OU: Abnormal high pressure, actuation of HPS
  2. [2] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 46 manufacturer document – copy from a distributor quote verified dirty outdoor heat exchanger.
  3. [3] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 46 manufacturer document – copy from a distributor quote verified closed stop valve in the refrigerant circuit.
  4. [4] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 46 manufacturer document – copy from a distributor quote verified outdoor temperature is out of operation range.
  5. [5] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 46 manufacturer document – copy from a distributor quote verified insufficient air flow or air by‑pass due to required space specifications not met.
  6. [6] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 46 manufacturer document – copy from a distributor quote verified faulty heat exchanger thermistor.
  7. [7] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 46 manufacturer document – copy from a distributor quote verified faulty expansion valve.
  8. [8] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 46 manufacturer document – copy from a distributor quote verified faulty main pcb.
  9. [9] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 46 manufacturer document – copy from a distributor quote verified non‑condensables and/or humidity in the refrigerant circuit.
  10. [10] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 46 manufacturer document – copy from a distributor quote verified clogged refrigerant circuit.
  11. [11] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 46 manufacturer document – copy from a distributor quote verified faulty outdoor unit fan motor.
  12. [12] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 46 manufacturer document – copy from a distributor quote verified clean the outdoor heat exchanger.
  13. [13] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 46 manufacturer document – copy from a distributor quote verified check that all stop valves of the refrigerant circuit are open.
  14. [14] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 46 manufacturer document – copy from a distributor quote verified check the outdoor temperature.
  15. [15] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 46 manufacturer document – copy from a distributor quote verified check the required space around the outdoor unit heat exchanger.
  16. [16] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 46 manufacturer document – copy from a distributor quote verified perform a check of the heat exchanger thermistor.
  17. [17] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 46 manufacturer document – copy from a distributor quote verified perform a check of the expansion valve.
  18. [18] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 46 manufacturer document – copy from a distributor quote verified perform a check of the main pcb.
  19. [19] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 46 manufacturer document – copy from a distributor quote verified check for the presence of non‑condensables and/or humidity in the refrigerant circuit.
  20. [20] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 46 manufacturer document – copy from a distributor quote verified check if the refrigerant circuit is clogged.
  21. [21] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 46 manufacturer document – copy from a distributor quote verified perform a check of the outdoor unit fan motor.