H0-00OU: Voltage/current sensor problem
Name in the manufacturer's documentation (service manual): OU: Voltage/current sensor problem
[1]
In plain words (editorial)
The outdoor unit reports a voltage/current sensor problem. The documentation lists the main PCB, the inverter PCB, power supply disturbances and air or moisture in the refrigerant circuit.
When to call a service technician: Call the installer – PCB and power supply checks are done inside the unit.
✎ editorial – written from the cited sources, not a manufacturer statement. Status: draft.
For technicians
Possible causes (source text)
- Faulty main pcb[2]
- Faulty inverter pcb[3]
- ▪ faulty or disturbance of the power supply (power supply must be within range of nominal operating voltage ±4%), ▪ power drop, ▪ short circuit[4]
- Non‑condensables and/or humidity in the refrigerant circuit[5]
- Clogged refrigerant circuit[6]
- Faulty outdoor unit fan motor[7]
Steps given by the manufacturer (source text)
- Perform a check of the main pcb[8]
- Perform a check of the inverter pcb[9]
- Check if the power supply is compliant with the regulations[10]
- Check for the presence of non‑condensables and/or humidity in the refrigerant circuit[11]
- Check if the refrigerant circuit is clogged[12]
- Perform a check of the outdoor unit fan motor[13]
⚠ Work on refrigerant circuits, mains electricity and PV DC wiring is for qualified technicians only.
The Polish page has more detail (plain-language explanation, safe checks, guides): Read in Polish →
Sources
Every statement has a footnote to the document and PDF page. “Quote verified” means the quote was found automatically in the text of that page.
- [1] Daikin Altherma 3 R F – ERGA04~08E + EHVH/X04+08S18+23E – Installer reference guide (4P629086-1D (2024.04)) , p. 254 official manufacturer document quote verified
H0-00 OU: Voltage/current sensor problem
- [2] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 47 manufacturer document – copy from a distributor quote verified
faulty main pcb.
- [3] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 47 manufacturer document – copy from a distributor quote verified
faulty inverter pcb.
- [4] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 47 manufacturer document – copy from a distributor quote verified
▪ faulty or disturbance of the power supply (power supply must be within range of nominal operating voltage ±4%), ▪ power drop, ▪ short circuit.
- [5] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 47 manufacturer document – copy from a distributor quote verified
non‑condensables and/or humidity in the refrigerant circuit.
- [6] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 47 manufacturer document – copy from a distributor quote verified
clogged refrigerant circuit.
- [7] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 47 manufacturer document – copy from a distributor quote verified
faulty outdoor unit fan motor.
- [8] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 47 manufacturer document – copy from a distributor quote verified
perform a check of the main pcb.
- [9] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 47 manufacturer document – copy from a distributor quote verified
perform a check of the inverter pcb.
- [10] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 47 manufacturer document – copy from a distributor quote verified
check if the power supply is compliant with the regulations.
- [11] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 47 manufacturer document – copy from a distributor quote verified
check for the presence of non‑condensables and/or humidity in the refrigerant circuit.
- [12] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 47 manufacturer document – copy from a distributor quote verified
check if the refrigerant circuit is clogged.
- [13] Daikin – Service manual Daikin Altherma 3 R F + W, ESIE20-13C – 2022.09 (PDF copy on installer site cncpompyciepla.pl) (ESIE20-13C) , p. 47 manufacturer document – copy from a distributor quote verified
perform a check of the outdoor unit fan motor.