PLDC bus voltage is too low
Name in the manufacturer's documentation (service manual): DC bus voltage is too low
[1]
This page only quotes the original English documentation. A plain-language explanation has not been written yet, so the page is not indexed by search engines.
For technicians
Possible causes (source text)
⚠ Work on refrigerant circuits, mains electricity and PV DC wiring is for qualified technicians only.
The Polish page has more detail (plain-language explanation, safe checks, guides): Read in Polish →
Sources
Every statement has a footnote to the document and PDF page. “Quote verified” means the quote was found automatically in the text of that page.
- [1] Gree Electric Appliances – Service Manual, wall-mounted R32 GWH..AG.. (Pular) and related (copy from distributor Gree Climat, Ukraine) , p. 102 manufacturer document – copy from a distributor checked manually
DC bus voltage is too low
- [2] Gree Electric Appliances – Service Manual, wall-mounted R32 GWH..AG.. (Pular) and related (copy from distributor Gree Climat, Ukraine) , p. 102 manufacturer document – copy from a distributor quote verified
Measure the voltage between position L and position N on the wiring board (XT). If it's lower than 150 VAC, please turn on the unit until the power voltage is increased to the normal range
- [3] Gree Electric Appliances – Service Manual, wall-mounted R32 GWH..AG.. (Pular) and related (copy from distributor Gree Climat, Ukraine) , p. 102 manufacturer document – copy from a distributor quote verified
If the AC input is normal, please replace the outdoor control board