Growatt · Growatt MOD TL3-X (three-phase grid inverter, 3–15 kW) · Procedure

How to switch off and restart a Growatt MOD inverter (including after Error 200)

Summary (editorial)

“Error 200” means an arc fault (AFCI) – it can only be reset manually after the cause is fixed. Switch DC and AC off, wait for the screen to go dark, have the strings checked, then restart.

✎ editorial – written from the cited sources, not a manufacturer statement. Status: draft.

From the manufacturer's documentation (English source wording, with page)

  1. If an Error 200 message is displayed, the buzzer alarms, an electric arc occurred in the PV system. The AFCI has tripped and the inverter is in permanent shutdown[1]
  2. A tripped AFCI can only be reset manually[2]
  3. Turn the DC & AC Switch to position OFF[3]
  4. Wait for the screen be off[4]
  5. Perform troubleshooting on the PV system: check the PV strings' open circuit voltage is normal or not[5]
  6. After the fault is rectified, restart the inverter: turn the DC & AC Switch to position ON[6]
  7. Do not work on the product during operation[7]
  8. Do not deactivate the AFCI permanently[8]
  9. Close the circuit breaker between the inverter and the grid; the inverter starts a countdown to the self-check and then connects to the grid[9]
  10. In normal operation the inverter indicator turns green[10]
  11. If you encounter any problems and cannot solve it, please contact customer service[11]

⚠ Work on refrigerant circuits, mains electricity and PV DC wiring is for qualified technicians only.

The Polish page has more detail (plain-language explanation, safe checks, guides): Read in Polish →

Sources

Every statement has a footnote to the document and PDF page. “Quote verified” means the quote was found automatically in the text of that page.

  1. [1] Installation & Operation Manual – MOD 3–15KTL3-X (GR-UM-212-A-05, AU ed. 2021-12) (GR-UM-212-A-05) , p. 19 official manufacturer document quote verified if an "error 200" message is displayed, the buzzer alarms, an electric arc occurred in
  2. [2] Installation & Operation Manual – MOD 3–15KTL3-X (GR-UM-212-A-05, AU ed. 2021-12) (GR-UM-212-A-05) , p. 19 official manufacturer document quote verified a tripped afci can only be reset manually.
  3. [3] Installation & Operation Manual – MOD 3–15KTL3-X (GR-UM-212-A-05, AU ed. 2021-12) (GR-UM-212-A-05) , p. 19 official manufacturer document quote verified turn the dc & ac switch to position "off".
  4. [4] Installation & Operation Manual – MOD 3–15KTL3-X (GR-UM-212-A-05, AU ed. 2021-12) (GR-UM-212-A-05) , p. 19 official manufacturer document quote verified wait for the screen be off.
  5. [5] Installation & Operation Manual – MOD 3–15KTL3-X (GR-UM-212-A-05, AU ed. 2021-12) (GR-UM-212-A-05) , p. 19 official manufacturer document quote verified check the pv strings' open circuit voltage is normal or not.
  6. [6] Installation & Operation Manual – MOD 3–15KTL3-X (GR-UM-212-A-05, AU ed. 2021-12) (GR-UM-212-A-05) , p. 19 official manufacturer document quote verified after the fault is rectified, restart the inverter:
  7. [7] Installation & Operation Manual – MOD 3–15KTL3-X (GR-UM-212-A-05, AU ed. 2021-12) (GR-UM-212-A-05) , p. 19 official manufacturer document quote verified do not work on the product during operation.
  8. [8] Installation & Operation Manual – MOD 3–15KTL3-X (GR-UM-212-A-05, AU ed. 2021-12) (GR-UM-212-A-05) , p. 19 official manufacturer document quote verified do not deactivate the afci permanently.
  9. [9] Installation & Operation Manual – MOD 3–15KTL3-X (GR-UM-212-A-05, AU ed. 2021-12) (GR-UM-212-A-05) , p. 19 official manufacturer document quote verified will start a countdown to the self-check,and after the self-check is normal,it will be
  10. [10] Installation & Operation Manual – MOD 3–15KTL3-X (GR-UM-212-A-05, AU ed. 2021-12) (GR-UM-212-A-05) , p. 19 official manufacturer document quote verified in normal operation,the leaves of the inverter indicator window will turn green.
  11. [11] Installation & Operation Manual – MOD 3–15KTL3-X (GR-UM-212-A-05, AU ed. 2021-12) (GR-UM-212-A-05) , p. 19 official manufacturer document quote verified problems during the debugging process and cannot solve it,please contact customer