Huawei · PV inverters · Huawei SUN2000-KTL-M1 (three-phase inverter, 3–10 kW, battery-ready)
Alarm 2104DC Terminal Temperature Abnormal
Name in the manufacturer's documentation (fault list): DC Terminal Temperature Abnormal
[1]
In plain words (editorial)
The DC terminal temperature is abnormal; the inverter shuts down. The manual names DC cables not of the recommended specification or oxidised, a DC connector not fully inserted, badly crimped terminals or wrong tightening torque.
When to call a service technician: Have an installer check the DC cables and connectors; if the fault persists, contact Huawei technical support.
✎ editorial – written from the cited sources, not a manufacturer statement. Status: draft.
For technicians
Possible causes (source text)
- The dc power cable is not of the recommended specifications or is oxidized.[2]
- The dc connector is not properly inserted.[3]
- The ot/od terminals of the dc cable are not crimped as required, or the tightening torque of the wiring terminals on the dc side does not meet the requirement.[4]
- The temperature of the dc terminal on mppt1 is abnormal.[5]
Steps given by the manufacturer (source text)
- Check whether the cables meet the requirements.[6]
- Check whether the dc connector is properly inserted.[7]
- Check whether the ot/od terminals are crimped as required and whether the tightening torque of wiring terminals meets the requirement.[8]
- Turn on the ac switch and dc switch, and restart the inverter.[9]
- Check whether the pv terminal cores are crimped properly.[10]
- Check whether the pv terminal models are correct.[11]
- Check whether pv terminals are loosely connected.[12]
- If the preceding items are normal, turn on the ac switch and dc switch, and restart the device. if the fault persists, contact the vendor or technical support.[13]
What the device does (source text)
- The device is shut down.[14]
⚠ Work on refrigerant circuits, mains electricity and PV DC wiring is for qualified technicians only.
The Polish page has more detail (plain-language explanation, safe checks, guides): Read in Polish →
Sources
Every statement has a footnote to the document and PDF page. “Quote verified” means the quote was found automatically in the text of that page.
- [1] Inverter Alarm Reference (Issue 14, 2026-06-15) (EDOC1100345192 Issue 14) , p. 99 official manufacturer document quote verified
2104 DC Terminal Temperature Abnormal
- [2] Inverter Alarm Reference (Issue 14, 2026-06-15) (EDOC1100345192 Issue 14) , p. 99 official manufacturer document quote verified
the dc power cable is not of the recommended specifications or is oxidized.
- [3] Inverter Alarm Reference (Issue 14, 2026-06-15) (EDOC1100345192 Issue 14) , p. 99 official manufacturer document quote verified
the dc connector is not properly inserted.
- [4] Inverter Alarm Reference (Issue 14, 2026-06-15) (EDOC1100345192 Issue 14) , p. 99 official manufacturer document quote verified
the ot/od terminals of the dc cable are not crimped as required, or the tightening torque of the wiring terminals on the dc side does not meet the requirement.
- [5] Inverter Alarm Reference (Issue 14, 2026-06-15) (EDOC1100345192 Issue 14) , p. 99 official manufacturer document quote verified
the temperature of the dc terminal on mppt1 is abnormal.
- [6] Inverter Alarm Reference (Issue 14, 2026-06-15) (EDOC1100345192 Issue 14) , p. 97 official manufacturer document quote verified
check whether the cables meet the requirements.
- [7] Inverter Alarm Reference (Issue 14, 2026-06-15) (EDOC1100345192 Issue 14) , p. 100 official manufacturer document quote verified
check whether the dc connector is properly inserted.
- [8] Inverter Alarm Reference (Issue 14, 2026-06-15) (EDOC1100345192 Issue 14) , p. 100 official manufacturer document quote verified
check whether the ot/od terminals are crimped as required and whether the tightening torque of wiring terminals meets the requirement.
- [9] Inverter Alarm Reference (Issue 14, 2026-06-15) (EDOC1100345192 Issue 14) , p. 100 official manufacturer document quote verified
turn on the ac switch and dc switch, and restart the inverter.
- [10] Inverter Alarm Reference (Issue 14, 2026-06-15) (EDOC1100345192 Issue 14) , p. 100 official manufacturer document quote verified
check whether the pv terminal cores are crimped properly.
- [11] Inverter Alarm Reference (Issue 14, 2026-06-15) (EDOC1100345192 Issue 14) , p. 100 official manufacturer document quote verified
check whether the pv terminal models are correct.
- [12] Inverter Alarm Reference (Issue 14, 2026-06-15) (EDOC1100345192 Issue 14) , p. 100 official manufacturer document quote verified
check whether pv terminals are loosely connected.
- [13] Inverter Alarm Reference (Issue 14, 2026-06-15) (EDOC1100345192 Issue 14) , p. 100 official manufacturer document quote verified
if the preceding items are normal, turn on the ac switch and dc switch, and restart the device. if the fault persists, contact the vendor or technical support.
- [14] Inverter Alarm Reference (Issue 14, 2026-06-15) (EDOC1100345192 Issue 14) , p. 99 official manufacturer document quote verified
the device is shut down.