LG · Heat pumps · LG Therma V Monobloc (air-to-water heat pump)
CH35Low pressure Error
Name in the manufacturer's documentation (service manual): Low pressure Error
[1]
In plain words (editorial)
The low pressure dropped excessively. The service manual names a defective low pressure sensor, fan, EEV, PCB or pipe sensor, refrigerant shortage or leakage, a damaged refrigerant pipe, covering or clogging of the unit (e.g. a clogged filter in heating mode) or a clogged service valve.
When to call a service technician: Make sure the unit is not covered or clogged; if the code repeats, contact an LG-authorised service technician or your installer.
✎ editorial – written from the cited sources, not a manufacturer statement. Status: draft.
For technicians
Possible causes (source text)
- Excessive decrease of low pressure[2]
- Defective low pressure sensor[3]
- Defective unit fan[4]
- Refrigerant shortage/leakage[5]
- Deformation because of damage of refrigerant pipe[6]
- Defective unit EEV[7]
- Covering / clogging (unit covering during the cooling mode / unit filter clogging during heating mode)[8]
- SVC valve clogging[9]
- Defective unit PCB(Inverter)[10]
- Defective unit pipe sensor[11]
⚠ Work on refrigerant circuits, mains electricity and PV DC wiring is for qualified technicians only.
The Polish page has more detail (plain-language explanation, safe checks, guides): Read in Polish →
Sources
Every statement has a footnote to the document and PDF page. “Quote verified” means the quote was found automatically in the text of that page.
- [1] LG Therma V Monobloc – Installation manual (MFL68026607 Rev.21) (MFL68026607 Rev.21_062126) , p. 278 official manufacturer document quote verified
35 Low pressure Error
- [2] LG Therma V Monobloc – Installation manual (MFL68026607 Rev.21) (MFL68026607 Rev.21_062126) , p. 278 official manufacturer document quote verified
Excessive decrease of low pressure
- [3] LG Therma V Monobloc – Installation manual (MFL68026607 Rev.21) (MFL68026607 Rev.21_062126) , p. 278 official manufacturer document quote verified
Defective low pressure sensor
- [4] LG Therma V Monobloc – Installation manual (MFL68026607 Rev.21) (MFL68026607 Rev.21_062126) , p. 278 official manufacturer document quote verified
Defective unit fan
- [5] LG Therma V Monobloc – Installation manual (MFL68026607 Rev.21) (MFL68026607 Rev.21_062126) , p. 278 official manufacturer document quote verified
Refrigerant shortage/leakage
- [6] LG Therma V Monobloc – Installation manual (MFL68026607 Rev.21) (MFL68026607 Rev.21_062126) , p. 278 official manufacturer document quote verified
Deformation because of damage of refrigerant pipe
- [7] LG Therma V Monobloc – Installation manual (MFL68026607 Rev.21) (MFL68026607 Rev.21_062126) , p. 278 official manufacturer document quote verified
Defective unit EEV
- [8] LG Therma V Monobloc – Installation manual (MFL68026607 Rev.21) (MFL68026607 Rev.21_062126) , p. 278 official manufacturer document quote verified
Covering / clogging (unit covering during the cooling mode / unit filter clogging during heating mode)
- [9] LG Therma V Monobloc – Installation manual (MFL68026607 Rev.21) (MFL68026607 Rev.21_062126) , p. 278 official manufacturer document quote verified
SVC valve clogging
- [10] LG Therma V Monobloc – Installation manual (MFL68026607 Rev.21) (MFL68026607 Rev.21_062126) , p. 278 official manufacturer document quote verified
Defective unit PCB(Inverter)
- [11] LG Therma V Monobloc – Installation manual (MFL68026607 Rev.21) (MFL68026607 Rev.21_062126) , p. 278 official manufacturer document quote verified
Defective unit pipe sensor