Mitsubishi Electric · Heat pumps · Mitsubishi Electric Ecodan PUZ-WM outdoor unit (R32)
E0Remote controller transmission error (E0) / signal receiving error (E4)
Name in the manufacturer's documentation (service manual): Remote controller transmission error (E0) / signal receiving error (E4)
[1]
In plain words (editorial)
The main remote controller cannot receive any transmission from the indoor unit. The service manual names a contact failure or miswiring of the remote controller transmission wire, or electrical noise on it.
When to call a service technician: Contact your installer or a Mitsubishi Electric service technician.
✎ editorial – written from the cited sources, not a manufacturer statement. Status: draft.
For technicians
Detection conditions (source text)
- Abnormal if main remote controller cannot receive normally any transmission from indoor unit of refrigerant address “0” for 3 minutes[2]
Possible causes (source text)
Steps given by the manufacturer (source text)
⚠ Work on refrigerant circuits, mains electricity and PV DC wiring is for qualified technicians only.
The Polish page has more detail (plain-language explanation, safe checks, guides): Read in Polish →
Sources
Every statement has a footnote to the document and PDF page. “Quote verified” means the quote was found automatically in the text of that page.
- [1] Mitsubishi Electric – Service Manual: Air to water heat pump units, outdoor unit PUZ-WM50VHA … PUZ-WM112YAA (OCH727 REVISED EDITION-A, 12/2023) (OCH727A (12/2023)) , p. 29 official manufacturer document quote verified
- [2] Mitsubishi Electric – Service Manual: Air to water heat pump units, outdoor unit PUZ-WM50VHA … PUZ-WM112YAA (OCH727 REVISED EDITION-A, 12/2023) (OCH727A (12/2023)) , p. 29 official manufacturer document quote verified
abnormal if main remote controller
- [3] Mitsubishi Electric – Service Manual: Air to water heat pump units, outdoor unit PUZ-WM50VHA … PUZ-WM112YAA (OCH727 REVISED EDITION-A, 12/2023) (OCH727A (12/2023)) , p. 29 official manufacturer document quote verified
contact failure at transmission
- [4] Mitsubishi Electric – Service Manual: Air to water heat pump units, outdoor unit PUZ-WM50VHA … PUZ-WM112YAA (OCH727 REVISED EDITION-A, 12/2023) (OCH727A (12/2023)) , p. 29 official manufacturer document quote verified
miswiring of remote controller
- [5] Mitsubishi Electric – Service Manual: Air to water heat pump units, outdoor unit PUZ-WM50VHA … PUZ-WM112YAA (OCH727 REVISED EDITION-A, 12/2023) (OCH727A (12/2023)) , p. 29 official manufacturer document quote verified
noise has entered into the
- [6] Mitsubishi Electric – Service Manual: Air to water heat pump units, outdoor unit PUZ-WM50VHA … PUZ-WM112YAA (OCH727 REVISED EDITION-A, 12/2023) (OCH727A (12/2023)) , p. 29 official manufacturer document quote verified
check disconnection or looseness of indoor
- [7] Mitsubishi Electric – Service Manual: Air to water heat pump units, outdoor unit PUZ-WM50VHA … PUZ-WM112YAA (OCH727 REVISED EDITION-A, 12/2023) (OCH727A (12/2023)) , p. 29 official manufacturer document quote verified
total wiring length: max. 500 m
- [8] Mitsubishi Electric – Service Manual: Air to water heat pump units, outdoor unit PUZ-WM50VHA … PUZ-WM112YAA (OCH727 REVISED EDITION-A, 12/2023) (OCH727A (12/2023)) , p. 29 official manufacturer document quote verified
diagnose remote controller (pac-if011b-e