Panasonic · Heat pumps · Panasonic Aquarea Monobloc, generation J (R32)
H42Compressor low pressure abnormality
Name in the manufacturer's documentation (service manual): Compressor low pressure abnormality
[1]
In plain words (editorial)
In heating mode the outdoor refrigerant pipe temperature went outside the expected range, which points to a problem in the refrigerant circuit or poor air flow at the outdoor unit.
When to call a service technician: Call a service technician with F-gas certification – this concerns the refrigerant circuit.
✎ editorial – written from the cited sources, not a manufacturer statement. Status: draft.
For technicians
Detection conditions (source text)
Possible causes (source text)
- Dust accumulation on the outdoor unit heat exchanger.[4]
- Air short circuit at outdoor unit.[5]
- 2 way valve partially closed.[6]
- Faulty outdoor unit fan motor.[7]
- Refrigerant shortage (refrigerant leakage).[8]
- Clogged expansion valve or strainer.[9]
- Faulty outdoor pipe temperature sensor.[10]
- Faulty outdoor unit main PCB (main).[11]
⚠ Work on refrigerant circuits, mains electricity and PV DC wiring is for qualified technicians only.
The Polish page has more detail (plain-language explanation, safe checks, guides): Read in Polish →
Sources
Every statement has a footnote to the document and PDF page. “Quote verified” means the quote was found automatically in the text of that page.
- [1] Service Manual – Mono Bloc Unit WH-MDC05J3E5 / WH-MDC07J3E5 / WH-MDC09J3E5 (PAPAMY2003034CE) , p. 164 manufacturer document – copy from a distributor quote verified
h42 compressor low pressure abnormality
- [2] Service Manual – Mono Bloc Unit WH-MDC05J3E5 / WH-MDC07J3E5 / WH-MDC09J3E5 (PAPAMY2003034CE) , p. 175 manufacturer document – copy from a distributor quote verified
when outdoor pipe temperature below -29°c or above 26°c is detected by the outdoor pipe temperature sensor
- [3] Service Manual – Mono Bloc Unit WH-MDC05J3E5 / WH-MDC07J3E5 / WH-MDC09J3E5 (PAPAMY2003034CE) , p. 175 manufacturer document – copy from a distributor quote verified
after 5 minutes compressor on
- [4] Service Manual – Mono Bloc Unit WH-MDC05J3E5 / WH-MDC07J3E5 / WH-MDC09J3E5 (PAPAMY2003034CE) , p. 175 manufacturer document – copy from a distributor quote verified
Dust accumulation on the outdoor unit heat exchanger.
- [5] Service Manual – Mono Bloc Unit WH-MDC05J3E5 / WH-MDC07J3E5 / WH-MDC09J3E5 (PAPAMY2003034CE) , p. 175 manufacturer document – copy from a distributor quote verified
Air short circuit at outdoor unit.
- [6] Service Manual – Mono Bloc Unit WH-MDC05J3E5 / WH-MDC07J3E5 / WH-MDC09J3E5 (PAPAMY2003034CE) , p. 175 manufacturer document – copy from a distributor quote verified
2 way valve partially closed.
- [7] Service Manual – Mono Bloc Unit WH-MDC05J3E5 / WH-MDC07J3E5 / WH-MDC09J3E5 (PAPAMY2003034CE) , p. 175 manufacturer document – copy from a distributor quote verified
Faulty outdoor unit fan motor.
- [8] Service Manual – Mono Bloc Unit WH-MDC05J3E5 / WH-MDC07J3E5 / WH-MDC09J3E5 (PAPAMY2003034CE) , p. 175 manufacturer document – copy from a distributor quote verified
Refrigerant shortage (refrigerant leakage).
- [9] Service Manual – Mono Bloc Unit WH-MDC05J3E5 / WH-MDC07J3E5 / WH-MDC09J3E5 (PAPAMY2003034CE) , p. 175 manufacturer document – copy from a distributor quote verified
Clogged expansion valve or strainer.
- [10] Service Manual – Mono Bloc Unit WH-MDC05J3E5 / WH-MDC07J3E5 / WH-MDC09J3E5 (PAPAMY2003034CE) , p. 175 manufacturer document – copy from a distributor quote verified
Faulty outdoor pipe temperature sensor.
- [11] Service Manual – Mono Bloc Unit WH-MDC05J3E5 / WH-MDC07J3E5 / WH-MDC09J3E5 (PAPAMY2003034CE) , p. 175 manufacturer document – copy from a distributor quote verified
Faulty outdoor unit main PCB (main).