Vaillant · Heat pumps · Vaillant aroTHERM plus with uniTOWER plus
F.731High-pressure switch open
Name in the manufacturer's documentation (service manual): High-pressure switch open
[1]
In plain words (editorial)
The high-pressure switch in the outdoor unit tripped – the refrigerant pressure is too high. The manual names too little heat taken away by the condenser, too low water flow (e.g. single-room controls closing in an underfloor heating system), a blocked dirt filter, or too low refrigerant flow.
When to call a service technician: Make sure the room/underfloor valves are not all closed. If it repeats, contact a heating engineer.
✎ editorial – written from the cited sources, not a manufacturer statement. Status: draft.
For technicians
Possible causes (source text)
- Refrigerant pressure too high; integrated high-pressure switch in the outdoor unit tripped[2]
- Insufficient energy output via the condenser[3]
- Too low a volume flow as a result of closing single room controls in an underfloor heating system[4]
- Refrigerant flow rate too low (e.g. EEV defective, 4-port diverter valve mechanically blocked, filter blocked)[5]
Steps given by the manufacturer (source text)
- Purging the building circuit[6]
- Check that the dirt filter that is in place is permeable[7]
- Inform customer service (refrigerant flow rate too low)[8]
- Cooling mode: check the fan unit for dirt[9]
- Check the high-pressure switch and high-pressure sensor[10]
- Reset the high-pressure switch and carry out a manual reset on the product[11]
⚠ Work on refrigerant circuits, mains electricity and PV DC wiring is for qualified technicians only.
The Polish page has more detail (plain-language explanation, safe checks, guides): Read in Polish →
Sources
Every statement has a footnote to the document and PDF page. “Quote verified” means the quote was found automatically in the text of that page.
- [1] Vaillant uniTOWER plus VIH QW 190/6 E – Operating, installation and maintenance instructions (0020291525_05) (0020291525_05) , p. 60 official manufacturer document quote verified
High-pressure switch open
- [2] Vaillant uniTOWER plus VIH QW 190/6 E – Operating, installation and maintenance instructions (0020291525_05) (0020291525_05) , p. 60 official manufacturer document quote verified
Refrigerant pressure too high. The
- [3] Vaillant uniTOWER plus VIH QW 190/6 E – Operating, installation and maintenance instructions (0020291525_05) (0020291525_05) , p. 60 official manufacturer document quote verified
Insufficient energy output via the
- [4] Vaillant uniTOWER plus VIH QW 190/6 E – Operating, installation and maintenance instructions (0020291525_05) (0020291525_05) , p. 60 official manufacturer document quote verified
Too low a volume flow as a result
- [5] Vaillant uniTOWER plus VIH QW 190/6 E – Operating, installation and maintenance instructions (0020291525_05) (0020291525_05) , p. 60 official manufacturer document quote verified
Inform customer service.
- [6] Vaillant uniTOWER plus VIH QW 190/6 E – Operating, installation and maintenance instructions (0020291525_05) (0020291525_05) , p. 60 official manufacturer document quote verified
Purging the building circuit
- [7] Vaillant uniTOWER plus VIH QW 190/6 E – Operating, installation and maintenance instructions (0020291525_05) (0020291525_05) , p. 60 official manufacturer document quote verified
Check that the dirt filter that is in
- [8] Vaillant uniTOWER plus VIH QW 190/6 E – Operating, installation and maintenance instructions (0020291525_05) (0020291525_05) , p. 60 official manufacturer document quote verified
Inform customer service.
- [9] Vaillant uniTOWER plus VIH QW 190/6 E – Operating, installation and maintenance instructions (0020291525_05) (0020291525_05) , p. 60 official manufacturer document quote verified
Cooling mode: Check the fan unit for
- [10] Vaillant uniTOWER plus VIH QW 190/6 E – Operating, installation and maintenance instructions (0020291525_05) (0020291525_05) , p. 60 official manufacturer document quote verified
Check the high-pressure switch and
- [11] Vaillant uniTOWER plus VIH QW 190/6 E – Operating, installation and maintenance instructions (0020291525_05) (0020291525_05) , p. 60 official manufacturer document quote verified
Reset the high-pressure switch and