Vaillant · Heat pumps · Vaillant aroTHERM plus with uniTOWER plus
F.817Freq. converter fault: Compressor
Name in the manufacturer's documentation (service manual): Freq. converter fault: Compressor
[1]
In plain words (editorial)
The frequency converter reports a compressor fault – the manual names a defect in the compressor (e.g. short circuit), in the frequency converter, or a defective or loose compressor cable.
When to call a service technician: Contact a competent heating engineer (installer or Vaillant customer service).
✎ editorial – written from the cited sources, not a manufacturer statement. Status: draft.
For technicians
Possible causes (source text)
Steps given by the manufacturer (source text)
⚠ Work on refrigerant circuits, mains electricity and PV DC wiring is for qualified technicians only.
The Polish page has more detail (plain-language explanation, safe checks, guides): Read in Polish →
Sources
Every statement has a footnote to the document and PDF page. “Quote verified” means the quote was found automatically in the text of that page.
- [1] Vaillant uniTOWER plus VIH QW 190/6 E – Operating, installation and maintenance instructions (0020291525_05) (0020291525_05) , p. 62 official manufacturer document quote verified
F.817 Freq. converter fault: Compressor
- [2] Vaillant uniTOWER plus VIH QW 190/6 E – Operating, installation and maintenance instructions (0020291525_05) (0020291525_05) , p. 62 official manufacturer document quote verified
Defect in the compressor (e.g. short circuit)
- [3] Vaillant uniTOWER plus VIH QW 190/6 E – Operating, installation and maintenance instructions (0020291525_05) (0020291525_05) , p. 62 official manufacturer document quote verified
Defect in the frequency converter
- [4] Vaillant uniTOWER plus VIH QW 190/6 E – Operating, installation and maintenance instructions (0020291525_05) (0020291525_05) , p. 62 official manufacturer document quote verified
Connection cable to the compressor is defective or loose
- [5] Vaillant uniTOWER plus VIH QW 190/6 E – Operating, installation and maintenance instructions (0020291525_05) (0020291525_05) , p. 62 official manufacturer document quote verified
Measure the winding resistance in the compressor
- [6] Vaillant uniTOWER plus VIH QW 190/6 E – Operating, installation and maintenance instructions (0020291525_05) (0020291525_05) , p. 62 official manufacturer document quote verified
Measure the frequency converter output between the three phases, (it must be > 1 kΩ)
- [7] Vaillant uniTOWER plus VIH QW 190/6 E – Operating, installation and maintenance instructions (0020291525_05) (0020291525_05) , p. 62 official manufacturer document quote verified
Check the wiring harness and plug connections